Q-2, r. 17.1 - Regulation respecting the regulatory scheme applying to activities on the basis of their environmental impact

Full text
212. The purge water discharged by a facility referred to in section 211 must
(1)  have a pH between 6 and 9.5;
(2)  have a total chlorine residual concentration below or equal to 0.1 mg/l;
(3)  have a concentration of suspended matters below or equal to 50 mg/l;
(4)  have a total phosphorous concentration below or equal to 1 mg/l.
The maintenance products used by a facility referred to in section 211 must not contain non-oxidizing biocides.
O.C. 871-2020, s. 212.
In force: 2020-12-31
212. The purge water discharged by a facility referred to in section 211 must
(1)  have a pH between 6 and 9.5;
(2)  have a total chlorine residual concentration below or equal to 0.1 mg/l;
(3)  have a concentration of suspended matters below or equal to 50 mg/l;
(4)  have a total phosphorous concentration below or equal to 1 mg/l.
The maintenance products used by a facility referred to in section 211 must not contain non-oxidizing biocides.
O.C. 871-2020, s. 212.